Our work / outlet, switch and circuit work

A stuck Lewisville GFCI and a panel with no ground wire to earth

The call was about a bathroom GFCI outlet that would not reset. While troubleshooting it, we checked the main electrical panel and found the grounding lug empty: no grounding electrode conductor connecting the panel to the earth. We replaced the GFCI, then ran and bonded a new #4 bare copper conductor to code-compliant ground electrodes.

What was happening

The call was about a bathroom GFCI outlet that would not reset. Swapping the receptacle was the simple part. While troubleshooting it, we took a routine look inside the main electrical panel.

What we found

The panel’s dedicated grounding lug was sitting completely empty. The ground wires from the individual circuits were connected along the bus bars, but the heavy bare copper grounding electrode conductor, the wire that connects the whole electrical system to ground rods or the steel in the foundation, was not landed in the panel.

Lights and outlets keep working without this wire, which is exactly why a defect like this goes unnoticed until a surge or a lightning strike finds it first.

The fix

We replaced the GFCI, then ran a new #4 bare copper grounding electrode conductor and bonded it from the panel’s grounding lug to code-compliant ground electrodes. The panel is now connected to the earth and meets the code requirement it was missing.

What to watch for at home

  • A GFCI that will not reset after you check the breaker and the other GFCI outlets in the house.
  • Outlets or lights that behave erratically.
  • A panel that has not been looked at in years, especially in an older home or after electrical work done by a previous owner.

Read more on why a missing panel ground wire matters, or see outlets, switches and circuits pricing and whole-home surge protection.

Real work

A stuck Lewisville GFCI and a panel with no ground wire to earth

Lewisville, TX, September 2026

Why they needed it

The bathroom GFCI would not reset, which was the reason for the call. The bigger problem was upstream. The main panel's dedicated grounding lug was empty: the ground wires from the individual circuits were landed on the bus bars, but the heavy copper conductor that should tie the service to the earth was not landed in the panel. Without that conductor anywhere on the service, surges and nearby lightning lose their designed path out of the house, and the service does not meet the National Electrical Code.

What we did

Replaced the bathroom GFCI receptacle, then ran a new #4 bare copper grounding electrode conductor and bonded it from the panel's grounding lug to code-compliant ground electrodes, so the electrical system is now connected to the earth.

About the price on this job: The GFCI outlet starting price covers one outlet. This visit went further: the main panel was missing its grounding electrode conductor, so it also took running and bonding a new #4 copper ground wire. Panel grounding work is quoted after a look at the panel.

On site

Photos from this job.

The grounding lug inside a main electrical panel, circled in red, with no ground wire in its clamp
Before. No ground wire in the clamp, so the panel had no connection to the earth.
A bare copper grounding electrode conductor running through the grounding clamp in the panel, circled in green
After. The bare copper ground wire through the clamp and on to the grounding electrodes.